Kehua Precision Air Conditioning WiseCol-M Series
WiseCol-M Series (7.5kW-20kW)
Air-cooled variable frequency room-level air conditioner
Green, efficient, and energy-saving refrigeration solutions.
Product Introduction
WiseCol-M Series (7.5kW–20kW) air-cooled inverter air conditioners are specifically customized for small and medium-sized computer rooms, communication base stations, and similar scenarios, equipped with intelligent inverter technology. As a vital component of the computer room, the air conditioner is tailored to the equipment environment, featuring constant temperature and humidity control, combined with a design of high airflow and low cooling differential to achieve rapid and uniform heat dissipation. It sets the benchmark for heavy-duty computer room cooling value with long lifespan, low energy consumption, and worry-free maintenance.
Customer value
Energy-efficient
- · Full-series intelligent inverter design, cooling capacity 20%–100% Stepless adjustment
- High annual energy efficiency ratio, achieving efficient cooling and energy savings.
- Equipped with a high-airflow EC fan, with optional noise-reduction components for quieter and more energy-efficient operation.
- · Uses low-power wet film humidification, saving energy and electricity, with a wide range of applications.
High intelligence
- Standard RS485 interface, enabling local and remote monitoring with intelligent operation and maintenance.
- Smart control system, capable of achieving Group control of 32 units., with timed polling and automatic fault switching functionality.
- 380Vac±15% ultra-wide grid adaptability, with phase sequence protection, automatic start upon power recovery, and delayed start functions.
- · 7-inch true-color extra-large touchscreenMulti-level password protection, tiered authorization management.
Highly reliable
- · Adopts a well-known brand inverter compressor to ensure reliable system operation.
- · 365 days × 24 hours All-weather operation, MTBF >100,000 hours
- · Ultra-wide operating temperature range, supports outdoor use -35℃ to 45℃ Operating environment
- · Standard oil separator, supports ultra-long pipeline operation, with maximum pipe length up to 60m
- Equipped with comprehensive system self-diagnostics, low refrigerant alarm, and multiple protection functions.
- The unit comes with quick-connect fittings, no welding required, and features a fully pull-out maintenance design.
Product Technical Specifications — Variable Frequency
Main power supply
Air supply method: Compatible with multiple air supply modes
Indoor unit characteristics and parameters (24°C/50%RH①)
- Cooling capacity: 7.5kW / 12.5kW / 20.0kW (corresponding to different models)
- Sensible cooling capacity: 6.8kW / 11.3kW / 18.0kW (corresponding to different models)
35°C/27%RH② Cooling capacity
- Cooling capacity: 9.5kW / 14.8kW (corresponding to different models)
Circulating air volume
- Circulating air volume: 2300 m³/h / 3100 m³/h / 5000 m³/h (corresponding to different models)
Humidification and heating capacity
- Heating capacity: 3kW (some models)
- Humidification capacity: 1.5kg/h (some models)
Unit dimensions and weight (indoor unit)
- Width: 550mm / 650mm / 800mm (corresponding to different models)
- Depth: 450mm / 650mm (corresponding to different models)
- Height: 1800mm (all series)
- Maximum operating current of the whole machine: 14.3A / 17.6A / 26.3A (corresponding to different models)
- Net weight: 93kg / 99kg / 103kg / 109kg / 144kg (corresponding to different models)
Outdoor unit
- Outdoor unit model: KHRN10 / KHRN17 / KHRN27 (corresponding to different models)
- Main power supply: 220V / 1PH / 50Hz
- Width: 728mm / 1080mm (corresponding to different models)
- Depth: 405mm (full series)
- Height: 762mm / 1370mm (corresponding to different models)
- Weight: 34kg / 53kg / 74kg (corresponding to different models)
Note: Unit return air conditions: ① Indoor return air 24°C/50%RH, outdoor 35°C; ② Indoor return air 35°C/27%RH, outdoor 35°C.
Standard R410A refrigerant · Unit comes standard with EC fan, electronic expansion valve, sight glass, and oil separator.
For other product technical requirements, please contact Kehua Company separately.
Product Technical Specifications — Variable Frequency
| Name | KHJA-B8AUV | KHJA-P8AUV | KHJA-B12AUV | KHJA-P12AUV | KHJA-B20AUV | KHJA-P20AUV |
|---|---|---|---|---|---|---|
| Main power supply | ||||||
| Air supply method | ||||||
| Indoor unit characteristics and parameters (24°C/50%RH①) | ||||||
| Cooling capacity (kW) | 7.5 | 7.5 | 12.5 | 12.5 | 20.0 | 20.0 |
| Sensible cooling capacity (kW) | 6.8 | 6.8 | 11.3 | 11.3 | 18.0 | 18.0 |
| 35°C/27%RH② Cooling capacity (kW) | ||||||
| Cooling capacity (kW) | 9.5 | 9.5 | 14.8 | 14.8 | — | — |
| Circulating air volume (m³/h) | ||||||
| Circulating air volume (m³/h) | 2300 | 2300 | 3100 | 3100 | 5000 | 5000 |
| Heating capacity (kW) | — | 3 | — | 3 | — | — |
| Humidification capacity (kg/h) | — | 1.5 | — | 1.5 | — | — |
| Unit width (mm) | 550 | 550 | 650 | 650 | 800 | 800 |
| Unit depth (mm) | 450 | 450 | 450 | 450 | 650 | 650 |
| Unit height (mm) | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 |
| Maximum operating current of the whole machine (A) | 14.3 | 14.3 | 17.6 | 17.6 | 26.3 | 26.3 |
| Net weight (kg) | 93 | 99 | 103 | 109 | 144 | 144 |
| Outdoor unit | ||||||
| Outdoor unit model | KHRN10 | KHRN10 | KHRN17 | KHRN17 | KHRN27 | KHRN27 |
| Outdoor unit parameters | ||||||
| Main power supply | 220V / 1PH / 50Hz | |||||
| Unit width (mm) | 728 | 728 | 728 | 728 | 1080 | 1080 |
| Unit depth (mm) | 405 | 405 | 405 | 405 | 405 | 405 |
| Unit height (mm) | 762 | 762 | 1370 | 1370 | 1370 | 1370 |
| Weight (kg) | 34 | 34 | 53 | 53 | 74 | 74 |
Note: Unit return air conditions: ① Indoor return air 24°C/50%RH, outdoor 35°C; ② Indoor return air 35°C/27%RH, outdoor 35°C.
Standard R410A refrigerant · Unit comes standard with EC fan, electronic expansion valve, sight glass, and oil separator.
For other product technical requirements, please contact Kehua Company separately.
.wcm-table-title{font-size:1.2rem;font-weight:650;color:#0a2540;margin:0 0 .8rem 0}
.wcm-table{width:100%;border-collapse:collapse;font-size:.82rem;min-width:900px}
.wcm-table th{background:#e6eff8;color:#0a2540;font-weight:600;padding:8px 6px;text-align:center;border-bottom:2px solid #cbdae8}
.wcm-table td{padding:6px 5px;border-bottom:1px solid #e2ebf3;text-align:center;vertical-align:middle}
.wcm-table tr:last-child td{border-bottom:none}
.wcm-group-header td{background:#dce6f2;font-weight:700;color:#0a2540;text-align:center;padding:5px}
.wcm-table-notes{margin-top:.8rem;font-size:.8rem;color:#3f6a87;line-height:1.6}
.wcm-table-notes p{margin:.2rem 0}