Kehua Data

Kehua Precision Air Conditioning WiseCol-M Series

⚡ Power/Cooling Capacity:8-20kVA
💰 Reference price:Negotiable
📂 Product Categories: precision air conditioner

WiseCol-M Series (7.5kW-20kW)

Air-cooled variable frequency room-level air conditioner

Green, efficient, and energy-saving refrigeration solutions.

Product Introduction

WiseCol-M Series (7.5kW–20kW) air-cooled inverter air conditioners are specifically customized for small and medium-sized computer rooms, communication base stations, and similar scenarios, equipped with intelligent inverter technology. As a vital component of the computer room, the air conditioner is tailored to the equipment environment, featuring constant temperature and humidity control, combined with a design of high airflow and low cooling differential to achieve rapid and uniform heat dissipation. It sets the benchmark for heavy-duty computer room cooling value with long lifespan, low energy consumption, and worry-free maintenance.

Customer value

Energy-efficient

  • · Full-series intelligent inverter design, cooling capacity 20%–100% Stepless adjustment
  • High annual energy efficiency ratio, achieving efficient cooling and energy savings.
  • Equipped with a high-airflow EC fan, with optional noise-reduction components for quieter and more energy-efficient operation.
  • · Uses low-power wet film humidification, saving energy and electricity, with a wide range of applications.

High intelligence

  • Standard RS485 interface, enabling local and remote monitoring with intelligent operation and maintenance.
  • Smart control system, capable of achieving Group control of 32 units., with timed polling and automatic fault switching functionality.
  • 380Vac±15% ultra-wide grid adaptability, with phase sequence protection, automatic start upon power recovery, and delayed start functions.
  • · 7-inch true-color extra-large touchscreenMulti-level password protection, tiered authorization management.

Highly reliable

  • · Adopts a well-known brand inverter compressor to ensure reliable system operation.
  • · 365 days × 24 hours All-weather operation, MTBF >100,000 hours
  • · Ultra-wide operating temperature range, supports outdoor use -35℃ to 45℃ Operating environment
  • · Standard oil separator, supports ultra-long pipeline operation, with maximum pipe length up to 60m
  • Equipped with comprehensive system self-diagnostics, low refrigerant alarm, and multiple protection functions.
  • The unit comes with quick-connect fittings, no welding required, and features a fully pull-out maintenance design.

Product Technical Specifications — Variable Frequency

Main power supply

Air supply method: Compatible with multiple air supply modes

Indoor unit characteristics and parameters (24°C/50%RH①)

  • Cooling capacity: 7.5kW / 12.5kW / 20.0kW (corresponding to different models)
  • Sensible cooling capacity: 6.8kW / 11.3kW / 18.0kW (corresponding to different models)

35°C/27%RH② Cooling capacity

  • Cooling capacity: 9.5kW / 14.8kW (corresponding to different models)

Circulating air volume

  • Circulating air volume: 2300 m³/h / 3100 m³/h / 5000 m³/h (corresponding to different models)

Humidification and heating capacity

  • Heating capacity: 3kW (some models)
  • Humidification capacity: 1.5kg/h (some models)

Unit dimensions and weight (indoor unit)

  • Width: 550mm / 650mm / 800mm (corresponding to different models)
  • Depth: 450mm / 650mm (corresponding to different models)
  • Height: 1800mm (all series)
  • Maximum operating current of the whole machine: 14.3A / 17.6A / 26.3A (corresponding to different models)
  • Net weight: 93kg / 99kg / 103kg / 109kg / 144kg (corresponding to different models)

Outdoor unit

  • Outdoor unit model: KHRN10 / KHRN17 / KHRN27 (corresponding to different models)
  • Main power supply: 220V / 1PH / 50Hz
  • Width: 728mm / 1080mm (corresponding to different models)
  • Depth: 405mm (full series)
  • Height: 762mm / 1370mm (corresponding to different models)
  • Weight: 34kg / 53kg / 74kg (corresponding to different models)

Note: Unit return air conditions: ① Indoor return air 24°C/50%RH, outdoor 35°C; ② Indoor return air 35°C/27%RH, outdoor 35°C.

Standard R410A refrigerant · Unit comes standard with EC fan, electronic expansion valve, sight glass, and oil separator.

For other product technical requirements, please contact Kehua Company separately.

WiseCol-M Series · Air-Cooled Variable Frequency Room-Level Air Conditioning · Green, Efficient, and Energy-Saving Cooling Solution

Product Technical Specifications — Variable Frequency

Name KHJA-B8AUV KHJA-P8AUV KHJA-B12AUV KHJA-P12AUV KHJA-B20AUV KHJA-P20AUV
Main power supply
Air supply method
Indoor unit characteristics and parameters (24°C/50%RH①)
Cooling capacity (kW) 7.5 7.5 12.5 12.5 20.0 20.0
Sensible cooling capacity (kW) 6.8 6.8 11.3 11.3 18.0 18.0
35°C/27%RH② Cooling capacity (kW)
Cooling capacity (kW) 9.5 9.5 14.8 14.8 — —
Circulating air volume (m³/h)
Circulating air volume (m³/h) 2300 2300 3100 3100 5000 5000
Heating capacity (kW) — 3 — 3 — —
Humidification capacity (kg/h) — 1.5 — 1.5 — —
Unit width (mm) 550 550 650 650 800 800
Unit depth (mm) 450 450 450 450 650 650
Unit height (mm) 1800 1800 1800 1800 1800 1800
Maximum operating current of the whole machine (A) 14.3 14.3 17.6 17.6 26.3 26.3
Net weight (kg) 93 99 103 109 144 144
Outdoor unit
Outdoor unit model KHRN10 KHRN10 KHRN17 KHRN17 KHRN27 KHRN27
Outdoor unit parameters
Main power supply 220V / 1PH / 50Hz
Unit width (mm) 728 728 728 728 1080 1080
Unit depth (mm) 405 405 405 405 405 405
Unit height (mm) 762 762 1370 1370 1370 1370
Weight (kg) 34 34 53 53 74 74

Note: Unit return air conditions: ① Indoor return air 24°C/50%RH, outdoor 35°C; ② Indoor return air 35°C/27%RH, outdoor 35°C.

Standard R410A refrigerant · Unit comes standard with EC fan, electronic expansion valve, sight glass, and oil separator.

For other product technical requirements, please contact Kehua Company separately.

.wcm-table-wrap{background:#fff;border-radius:16px;padding:1rem 1rem 0.8rem;box-shadow:0 2px 10px rgba(0,0,0,0.02);border:1px solid #edf2f7;overflow-x:auto;margin:1.8rem auto;max-width:1100px}
.wcm-table-title{font-size:1.2rem;font-weight:650;color:#0a2540;margin:0 0 .8rem 0}
.wcm-table{width:100%;border-collapse:collapse;font-size:.82rem;min-width:900px}
.wcm-table th{background:#e6eff8;color:#0a2540;font-weight:600;padding:8px 6px;text-align:center;border-bottom:2px solid #cbdae8}
.wcm-table td{padding:6px 5px;border-bottom:1px solid #e2ebf3;text-align:center;vertical-align:middle}
.wcm-table tr:last-child td{border-bottom:none}
.wcm-group-header td{background:#dce6f2;font-weight:700;color:#0a2540;text-align:center;padding:5px}
.wcm-table-notes{margin-top:.8rem;font-size:.8rem;color:#3f6a87;line-height:1.6}
.wcm-table-notes p{margin:.2rem 0}